MXT03S Online Flow Monitor for Drainage Networks
Category:
Online Flow Monitor for Drainage Pipe Networks
Qualifications and Honors
Product Description
Product Package: MXT03 Host Unit + MXS05D Current Meter
Product Overview
The MXT03S series online flow monitor for drainage networks is a dedicated device designed specifically for monitoring flow in sewer systems. Featuring an ultra-low-power microcontroller, it operates on battery power and incorporates network communication, enabling real-time, online monitoring of water levels and flow rates without requiring external power supplies, fiber-optic links, or pole-mounted installations. It employs a single-point ultrasonic Doppler velocity sensor to measure liquid level and flow velocity upstream of the sensor, all while preserving the natural flow field.
Product Features
● In compliance with the SL651-2014 Hydrological Monitoring Data Communication Protocol – Communication Protocol
● Employs a 32-bit ultra-low-power microcontroller, with a standby current of less than 35 µA.
● Powered by a single-use, high-capacity battery; under standard operating conditions, the battery replacement cycle is no less than 2 years.
● IP68-rated design, resistant to water ingress;
● Explosion-proof rating: Exia IIC T4 Ga;
● The housing is made of 316 stainless steel, offering excellent resistance to corrosion, acids, and alkalis, as well as impact resistance, making it suitable for use in sewage networks.
● Onboard temperature and humidity sensor for continuous monitoring of the enclosure’s environmental conditions;
● Onboard attitude sensor: when the device is moved illegally, it automatically sends an alert to the platform.
● High measurement accuracy, wide measurement range; capable of measuring both weak and strong currents.
● Highly sensitive, with high resolution, and not limited by the minimum flow velocity.
● Fast response time, capable of measuring both instantaneous and average flow velocity;
● Measurement linearity, with no calibration curve required. K, C value;
● Supports remote parameter configuration and monitoring, as well as remote device maintenance.
● Supports on-site configuration and maintenance via Bluetooth;
● It adopts a modular design, allowing direct replacement of the communication module without replacing the motherboard.
Technical Specifications
Host Parameters
|
Project |
Parameter Metrics |
|
CPU |
Industrial-grade 32-bit low-power Processor usage |
|
FLASH |
16 MB, capable of storing two years’ worth of measurement data, with automatic online upload to the database. |
|
Wireless communication |
Supports 4G/NB-IoT communication and private network communication. |
|
Operating system |
Proprietary operating system |
|
Bluetooth communication |
Supports local operations and maintenance of parameters via a mobile app. |
|
Sensor interface |
It can be externally connected to pressure sensors and Doppler flow meters to collect data on pipeline network flow velocity, flow rate, and water level. |
|
Temperature and humidity acquisition |
The motherboard features a built-in temperature and humidity sensor, enabling real-time monitoring of the internal operating environment’s temperature and humidity. |
|
Pose Acquisition |
Built-in health monitoring module (posture, status) for remote device status monitoring. |
|
Communication antenna |
External N‑type communication antenna and Bluetooth antenna enable both long-range wireless communication and short-range wireless communication. |
|
Power supply battery |
Standard configuration includes a 1080 Wh single-use lithium‑thionyl chloride battery, enabling 5-minute data acquisition and 30-minute reporting, with support for two years of maintenance-free operation. |
|
Power consumption |
Under standard configuration, the standby current consumption does not exceed 35 µA. |
|
Operating temperature |
-30~+70ºC |
|
Storage temperature |
-40~+85ºC |
|
Operating humidity |
95% (no condensation) |
|
Installation method |
Wellbore Support Installation |
|
Protection rating |
IP68 |
|
Housing material |
316L stainless steel body |
|
External dimensions |
φ140x208mm |
|
Overall machine weight |
5.1kg |
Current meter parameters
MXS05DS Doppler Current Meter MXS05DV2 Doppler Current Meter


| Item | Parameter Metrics | Parameter Metrics |
| Product Specifications |
Unidirectional |
Two-way |
| Operating frequency |
2M |
2M |
| Flow velocity measurement |
Flow velocity measurement employs the Doppler ultrasonic measurement principle. Flow rate is calculated using the “velocity-area method.” |
Flow velocity measurement employs the Doppler ultrasonic measurement principle. Flow rate is calculated using the “velocity-area method.” |
| Liquid level measurement | Adopts the principle of pressure measurement. | Adopts the principle of pressure measurement. |
| Flow rate range |
0.03 m/s ~ 5.0 m/s |
±0.03 m/s ~ ±5.0 m/s |
|
Flow velocity accuracy |
0.5%±0.001 m/s | 0.5%±0.001 m/s |
| Flow velocity resolution | 0.001m/s | 0.001m/s |
| Liquid level range | 10m | 10m |
| Level accuracy | 0.3%F.S | 0.3%F.S |
| Liquid level resolution | 1mm | 1mm |
| Operating temperature | -25℃ to 55℃ | -25℃ to 55℃ |
| Installation method | Bracket fixed installation | Bracket fixed installation |
|
Protection rating |
IP68 |
IP68 |
|
Operating voltage |
DC 7.5-15V |
DC 7.5-15V |
|
Power consumption |
Less than 0.5 W |
Less than 0.5 W |
| Communication interface | RS485 MODBUS protocol | RS485 MODBUS protocol |
| Sensor size | 200*50*30mm | 235*65*35mm |